Minuteman SNMP-32 Series Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Redes Minuteman SNMP-32 Series. NetAgent Utility V3.30 Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir

Resumo do Conteúdo

Página 1 - NetAgent

NetAgent UPS SNMP Agent User’s Manual

Página 2

3.2 Pictures of NetAgent NetAgent II(BN,BK,CK Series) BN506 BN514 BK514 CK504 BN505 BN513 BK513 NetAgent Mini (DK Series) DK530 DK520 D

Página 3

3.3 NetAgent Package Contents Netagent has three models: “Internal/External”; “1 phase/3 phase”; and “1 port/3 port”. The different model has differen

Página 4

♦ 3 Port NetAgent (Internal / External) : LED Table Yellow Red Green Status Solid Off Solid Off Solid ON Power ON Flashing Solid ON Soli

Página 5

3.5 NetAgent Mini Out looking NetAgent Mini External NetAgent Mini Internal Module To UPSTo LAN (LAN Port LED) Status LED To LAN (LAN Port LE

Página 6 - Chapter1. Introduction

Chapter 2. NetAgent UPS Installation Before using the NetAgent, the proper hardware and software configuration is necessary. Hardware installation

Página 7 - Section2. Applications

Chapter 3. NetAgent, UPS and Network Connection NetAgent II and NetAgent Mini provides External and Internal model for different UPS interface requir

Página 8

Section2. Install the NetAgent Mini with UPS and Network NetAgent Mini - External NetAgent Mini -Internal To UPSTo DC AdapterTo UPS To LANTo L

Página 9 - Section3. NetAgent Models

Chapter 4. Using Netility Setup IP.Update Firmware Section1. Install Netility  Insert NetAgent Utility CD to the CD-ROM driver and execute Netili

Página 10 - Fig.4 Pictures of NetAgent

 NetWork Selection After execute Netility, Netility would search computer’s internet card automatically, or, click on Network Selection from the main

Página 11 - Enternal NetAgent Mini

Advanced:Advanced Netagent UPS Setting In order to ensure the secure management of UPS, Netility provides two protecting function: Netility Password A

Página 12 - LED Table

User Guide for the NetAgent Version 3.30 Firmware version 2.35 Copyright Information Copyright © 2000-2004, Mega System Technologies, Inc. All right

Página 13

Note:Net Agent provided well-considerable protection function. If uploading was interrupted and raised data in incomplete, Net Agent will keep its de

Página 14

Chapter 5. UPS Web management by NetAgent Section1. Introduction After finishing NetAgent installation, including hardware installation and IP setting

Página 15

2.1 Information Sub-Menu : 2.1.1 System Status 2.1.2 Basic Information 2.1.3 Current Status 2.1.4 Remote Control 2.1.5 Meter/Chart 2.1.6 Environmen

Página 16

2.1.2 Basic Information This page is to show UPS basic information. Values here are either provided by the UPS or they are user settings from the Conf

Página 17 - Section2. Using Netility

Fig.21 Current Status 2.1.4 Remote Control This page is to provide remote UPS test functions. Choose the test item, then click on 'Apply' t

Página 18

2.1.5 Meter/Chart This page displays temperature, capacity, load, voltage..etc of the UPS by appearing with metres diagrams. Fig.23 Meter/Chart 2.1.6

Página 19

Fig.24 Environment Sensors - NetFeeler Lite 2.2 Configuration Sub-Menu : 2.2.1 UPS Configuration 2.2.2 UPS On/Off Schedule 2.2.3 Network 2.2.4 SN

Página 20

Last Battery Replaced Date ( mm/dd/yyyy) This section is to record the date when the UPS battery was last replaced. UPS Recorded UPS Data Log T

Página 21 - Section1. Introduction

2.2.2 UPS On/Off Schedule This page is to schedule On/Off time for the UPS. Weekly Schedule This section is to set the time to turn on/off the UPS

Página 22 - Fig.19 System Status

Primary DNS Server IP This section is to set NetAgent primary DNS Server IP address. Secondary DNS Server IP This section is to set NetAgent sec

Página 23 - Fig.20 Basic Information

Contents Chapter1. Introduction_________________________________________ 1 Section1. Features __________________________________________ 1 Section2. A

Página 24 - Fig.22 Remote Control

Trap Notification Receiver IP Address This section is to set receivers IP address for receiving traps sent by NetAgent. It is valid for up to 8 IP

Página 25 - Fig.23 Meter/Chart

2.2.5 Email This page is to set Email details for use by NetAgent. Email Server This section is to set NetAgent Email Server . Sender’s Email Ad

Página 26

2.2.6 WEB/Telnet This page is to set up the User Account in NetAgent. User Name This section is to set a user name for NetAgent web pages. It is v

Página 27 - Fig.25 UPS Configuration

2.2.8 NetFeeler Lite This page is to set Environment sensors-NetFeeler Lite configurations. Critical UnderRun This section is to set the lowest cr

Página 28 - 2.2.3 Network

2.3 Log Information Sub-Menu : 2.3.1 Event Log 2.3.2 Data Log 2.3.3 Save Data Log Note: This page’s selection would differ according to the differn

Página 29 - 2.2.4 SNMP

Fig.35 Date Log 2.3.3 Save Data Log This function is to record RS232 UPS’s voltage, frequency, load, capacity, temperature..etc to save as another fi

Página 30 - Fig.28 SNMP

Chapter 6. Telnet (Remote Monitoring) Section1. Introduction NetAgent supports multiple Network Management systems and LAN protocols. After finishing

Página 31 - 2.2.5 Email

Fig.40 NetAgent Telnet window ♦ Set IP Address. This function allows you to setup IP Address, Gateway Address, Subnet Mask parameters. ♦ Set SNMP MI

Página 32 - Fig.31 System Time

Chapter 7. ClientMate - Windows Shutdown Utility ClientMate is a utility for connecting to the RUPS 2000, UPSilon 2000 and NetAgent. This utility is

Página 33 - 2.2.9 Language

2.1 Configuration When the ClientMate gets the signal from the NetAgent about the AC power failure or battery low signals, the ClientMate will based o

Página 34 - Fig.34 Event Log

2.1.5 Meter/Chart________________________________________ 20 2.1.6 Environment Sensors-NetFeeler Lite ____________________ 20 2.2 Configuration_______

Página 35 - Fig.36 Save Data Log

♦ When Battery Low, commence computer shutdown sequence in xx Min. To configure the time delay between the Battery Low and system shutdown. ♦ Notify

Página 36

2.4 IP address of connection Status ICON Description Already connect to NetAgent UPS at IP 211.21.67.51 Does not connect to any NetAgent. 2.5 A

Página 37

Chapter 8. SNMPView – Windows Based UPS Management System SNMPView is a software to remotely monitor and control multiple UPS connected to a netwo

Página 38 - Section2. Using ClientMate

Section3. Install SNMPView 3.1 Install SNMPView  Put the NetAgent Utility CD into the CD driver. And execute the SNMPView program.  After installati

Página 39

3.2 Using SNMPView When use SNMP view at the first time, the system will ask for input the user's lease enter the default value as follows to sta

Página 40

3.3 SNMPView Buttons Enh all SNMP hosts that supports Public group and etAgent on network and in the main umerate : Searcdisplay them on the screen

Página 41

3.3.2 ADD UPS Click “Add UPS” to enter the IP address of the UPS manually. Once entered, the UPS will be shown on the main list. 3.3.3 DELETE UPS Cli

Página 42

“Email” Tab Click the “Email” tab from the settings windows to configure the SNMPView E-mail Warning configuration, diagram shown below: ♦ Sender Disp

Página 43 - Section3. Install SNMPView

Trap List Double click to edit the Trap settings. This sets the trap notification. UPS Loading This determines the UPS loading. Double t

Página 44

“Meter” Tab temperature of the UPS, in Fahrenheit The “Meter” tab displays the following information; ♦ Input Voltage: Show the voltage input from A

Página 45

Section3. Install SNMPView__________________________________ 38 3.1 Install SNMPView ______________________________________ 38 3.2 Using SNMPView ____

Página 46

“Digital” Tab Display (highlighted in blue) thcurrent input and oute put voltage, put frequency, battery capacity, U t als minimum encountered values

Página 47

“Control” Tab nother 1 minute. • Flash LED: Flash the UPS’s LED display. (Optional function of the UPS) • Cancel Shutdown: The UPS will cancel the “

Página 48

3.3.7 VIEW Lar ge Icon View mall Icon View S Detail View 47

Página 49

3.3.8 EVENT LOG • This button records and lists events for a particular UPS. 3.3.9 DATA LOG • Records data of all UPS listed. 3.3.10 OPTION Sets

Página 50

MENU Device Add Group • Add a new Group folder into the main list User to enter group name • Export Configuration Save the configuration in .dat c

Página 51

Help • Contents: This help menu • About Gives the current SNMP version, license and contact /fo mail. in50

Página 52

Appendix - Update the fiing convenient methods for user to update the late 1. nload Firmware” function under Netility to update it (suitable for all

Página 53

4. h Again, the password here is the one been set at Netility, if did not set anything before, Use IE browser to update (suitable for BK,CK,DK vers

Página 55

Chapter1. Introduction Section1. Features NetAgent is a new generation SNMP (Simple Network Management Protocol) monitoring product. Not only c

Página 56 - Appendix - Update the fi

Section2. Applications 2.1 NetAgent makes your UPS on the Internet When the UPS install the NetAgent, the system manager could check each and every UP

Página 57

Fig.1 NetAgent connection Software Fig.2 3 Port NetAgent II Diagram 3

Página 58

Section3. NetAgent Models 3.1 NetAgent Models NetAgent II Model P/N Package Contents Internal/External 1/3 Port 1/3 phase504 1. 1Port Internal 2. N

Comentários a estes Manuais

Sem comentários